Wire Gauge Calculator

AWG to mm² conversion and voltage drop for copper or aluminum

Use 0 for 1/0, −1 for 2/0, −2 for 3/0 and −3 for 4/0. Solid-wire dimensions.
Distance from the source to the load, not the round trip.
A
V
The NEC recommends 3 % on a branch circuit and 5 % overall. It is an informational recommendation, not a pass/fail rule.
Voltage drop with this wire—
Voltage drop in volts—
Smallest standard AWG that stays within your limit—
Wire diameter (mm)—
Cross-section area (mm²)—
Wire diameter (inches)—
Resistance per 1,000 ft—
🎰 15 Global Lotteries + 12 Smart Number Pickers
Powerball · Mega Millions · EuroMillions · UK Lotto — Zodiac, Birthday, Dream, AI & more

Wire gauge (AWG) to diameter and area

American Wire Gauge is defined by two fixed points: 36 AWG is 0.005 inches in diameter and 0000 (4/0) AWG is 0.46 inches, with each step a constant ratio, the 39th root of 92. In millimeters the diameter is d = 0.127 mm × 92^((36 − n) ÷ 39), where n is the gauge number (−1 for 00, −2 for 000, −3 for 0000). The cross-section is π/4 × d².

Example: 12 AWG gives d = 0.127 × 92^(24/39) = 2.053 mm, area 3.309 mm²; 10 AWG is 2.588 mm and 5.261 mm². Lower numbers are thicker wire. These are solid-wire values; stranded wire of the same gauge differs slightly.

How the voltage drop is calculated

Voltage drop is current times resistance (V = I × R). The resistance of a conductor is its resistivity times its length divided by its cross-section. This tool uses 1.72 × 10⁻⁸ Ω·m for annealed copper and 2.82 × 10⁻⁸ Ω·m for aluminum (20 °C), counts both the outbound and return conductor on a single-phase circuit, and multiplies by √3 for three-phase.

Example: 12 AWG copper, 100 ft one way, 15 A at 120 V, single-phase: resistance is about 1.584 Ω per 1,000 ft, so the drop is 4.75 V = 3.96 %. To hold it to 3 % you would need 4.37 mm² or more, which means 10 AWG (5.26 mm²). Switching to 10 AWG brings the drop down to 2.99 V = 2.49 %.

The 3 % and 5 % guideline

The National Electrical Code includes an informational note recommending that branch-circuit conductors be sized to prevent a voltage drop above 3 % at the farthest outlet, and that the total drop across feeders and branch circuits stay within 5 %. Because it is a recommendation, your local inspector and the equipment maker’s requirements still decide what is acceptable.

What this calculator does not do

  • Ampacity. How much current a wire can safely carry depends on insulation, temperature, bundling and the code tables. This tool does not check it, so never size a wire on voltage drop alone.
  • Temperature and stranding. Resistivity is for 20 °C; hot conductors have higher resistance.
  • Metric sizes. To compare with mm² cable ratings, use the cross-section result above.

Have a licensed electrician do the wiring to your local code. For power calculations, see the Ohm’s law calculator, and for running-cost questions the electricity cost calculator.

Sources

Last checked: 2026-10-31

Frequently Asked Questions

What is the formula for AWG diameter?
Diameter in mm = 0.127 × 92^((36 − n) ÷ 39), where n is the AWG number. It follows from 36 AWG = 0.005 in and 0000 AWG = 0.46 in.
What size wire do I need for a long run?
It depends on current, voltage, length, material and how much drop you accept. Enter your values above to see the smallest standard AWG that stays within 3 % or 5 %, then confirm the ampacity with a licensed electrician.
What voltage drop is acceptable?
The NEC informational note recommends no more than 3 % on a branch circuit and 5 % across feeder plus branch circuit. Some equipment needs less.
Is aluminum wire bigger than copper for the same drop?
Yes. Aluminum has higher resistivity (2.82 vs 1.72 × 10⁻⁸ Ω·m), so you need a larger cross-section for the same voltage drop.
Why does the tool use twice the length for single-phase?
Current flows out on one conductor and back on the other, so the resistance that counts is that of both conductors. Three-phase balanced circuits use √3 times the one-way length instead.

Bookmarks